General

Protected Premises Emergency Control Functions (Relays length limitations)

Posted on June 14, 2018 by Gsurface

Fire alarm relays are used to accomplish a number of functions: anywhere from shutting down an air handling unit, releasing an electrically help door, activating an exhaust fan, or activating elevator recall function.  Because the requirements of monitoring of the… Continue Reading →

General

Fire Pump Disconnecting Means

Posted on June 13, 2018 by Gsurface

The disconnecting means for the fire pump shall be marked as such as well as locked in the on position. During a fire condition, when the sprinkler system is activated, the fire pump shall run until the responding emergency unit,… Continue Reading →

General

Dry-Type Sprinkler Monitoring

Posted on June 12, 2018 by Gsurface

17.16.2.2.2 Dry-Type Sprinkler. (1) A pressure supervisory signal-initiating device for a dry- pipe sprinkler system shall indicate both high- and low- pressure conditions. (2) The off-normal signal shall be initiated when the pressure increases or decreases by 10 psi (70… Continue Reading →

General

Stair Pressurization Fans Shutdown

Posted on June 11, 2018 by Gsurface

Stair Pressurization is provided to allow building occupants to safely evacuate a building using the stair cases. Fans are provided to supply air into the staircase upon activation of an associated alarm condition. The idea is to pressurize the stairs… Continue Reading →

General

Elevator Lobby Smoke Detection

Posted on June 9, 2018 by Gsurface

21.3.5* A lobby smoke detector shall be located on the ceiling within 21 It (6.4 m) of the centerline of each elevator door within the elevator bank under control of the detector. 21.3.3 Unless otherwise required by the authority having… Continue Reading →

General

Smoke Detection For Fire Alarm Equipment

Posted on June 8, 2018 by Gsurface

  10.15* Protection of Fire Alarm System. In areas that are not continuously occupied, automatic smoke detection shall be provided at the location of each fire alarm control unit(s), notification appliance circuit power extenders, and supervis- ing station transmitting equipment… Continue Reading →

General

As-builts and Operations Manual

Posted on June 7, 2018 by Gsurface

14.6.1.1 A set of reproducible as-built installation drawings, operation and maintenance manuals, and a written sequence of operation shall be provided to the building owner or the owner’s designated representative.   Looking for our NICET Fire Alarm System Exam Study… Continue Reading →

General

Manual Pull Stations

Posted on June 6, 2018 by Gsurface

Saw this install at a project in a newly built warehouse. The blue colored pull station is there to release the standpipe solenoid. The standpipe is dry, not holding water, because it is installed in a huge freezer where if… Continue Reading →

General

Manual Fire Alarm Box

Posted on June 5, 2018 by Gsurface

The idea behind requiring a manual fire alarm box is to allow a means to initiate an alarm signal to Central Station in the event the fire detector or sprinkler water flow device is out of service or being tested.… Continue Reading →

General

Smoke Detector Installed on Peak Ceiling

Posted on June 4, 2018 by Gsurface

Below is an installation of a smoke detector on a peaked ceiling. NFPA 72 says that such detector shall be installed within 36 inches of the peak of the ceiling. 17.7.3.3* Peaked. Detectors shall first he spaced and located within… Continue Reading →

General

Post navigation

Older Articles
Newer Articles
Follow on Instagram
This error message is only visible to WordPress admins

Error: No posts found.

Make sure this account has posts available on instagram.com.

Recent Posts

  • An Introduction to Fire Alarm Systems
  • NICET Fire Alarm Systems Levels 1 & 2 Study Guide
  • 2018 NICET Fire Alarm Systems Level 2 Study Guide
  • 2018 NICET Fire Alarm Systems Level 1 Study Guide
  • NICET Certification Fire Alarm System Pop Quiz Question-Concealed Duct Detector

Recent Comments

    Archives

    • February 2020
    • July 2019
    • June 2019
    • October 2018
    • September 2018
    • July 2018
    • June 2018
    • August 2016
    • March 2016
    • February 2016
    • January 2016
    • December 2015

    Meta

    • Register
    • Log in
    • Entries feed
    • Comments feed
    • WordPress.org

    Categories

    • General
    • News
    • Pop Quiz
    • Videos
    © 2025 Fire Alarms Certified. All rights reserved.
    Hiero by aThemes