Spot-Type smoke detectors located on the ceiling

Posted on June 19, 2018 by Gsurface

Below is a picture of an explosion proof spot-type smoke detector installed in an electrical room in a parking garage.  The detector is installed as per NFPA 72  17.7.3.2.1.   NFPA 72  17.7.3.2.1 – * Spot-type smoke detectors shall be located on… Continue Reading →

General

Two-Way, In-Building Emergency Communications Systems

Posted on June 18, 2018 by Gsurface

NFPA 72 specifies the locations where, when provided, a two-way telephone communications equipment shall be installed.  When provided, the telephone equipment is to be used by the fire service to communicate between an area of a building and a constantly… Continue Reading →

General

Dedicated Function Fire Alarm Systems

Posted on June 16, 2018 by Gsurface

A dedicated function fire alarm system includes an elevator recall control and supervisory control unit; where a smoke control panel would be installed to monitor smoke detection used for elevator recall.  Also, a dedicated function fire alarm system used specifically… Continue Reading →

General

Support for Power-Limited Fire Alarm (PLFA) Circuit Cables

Posted on June 14, 2018 by Gsurface

The support requirements for fire alarm circuit conductors can be found in the National Electrical Code.  The NEC specifies that Power-Limited Fire Alarm cables be supported to building structure using an approved method at intervals not exceeding 18 inches.  Approved… Continue Reading →

General

Protected Premises Emergency Control Functions (Relays length limitations)

Posted on June 14, 2018 by Gsurface

Fire alarm relays are used to accomplish a number of functions: anywhere from shutting down an air handling unit, releasing an electrically help door, activating an exhaust fan, or activating elevator recall function.  Because the requirements of monitoring of the… Continue Reading →

General

Fire Pump Disconnecting Means

Posted on June 13, 2018 by Gsurface

The disconnecting means for the fire pump shall be marked as such as well as locked in the on position. During a fire condition, when the sprinkler system is activated, the fire pump shall run until the responding emergency unit,… Continue Reading →

General

Dry-Type Sprinkler Monitoring

Posted on June 12, 2018 by Gsurface

17.16.2.2.2 Dry-Type Sprinkler. (1) A pressure supervisory signal-initiating device for a dry- pipe sprinkler system shall indicate both high- and low- pressure conditions. (2) The off-normal signal shall be initiated when the pressure increases or decreases by 10 psi (70… Continue Reading →

General

Stair Pressurization Fans Shutdown

Posted on June 11, 2018 by Gsurface

Stair Pressurization is provided to allow building occupants to safely evacuate a building using the stair cases. Fans are provided to supply air into the staircase upon activation of an associated alarm condition. The idea is to pressurize the stairs… Continue Reading →

General

Elevator Lobby Smoke Detection

Posted on June 9, 2018 by Gsurface

21.3.5* A lobby smoke detector shall be located on the ceiling within 21 It (6.4 m) of the centerline of each elevator door within the elevator bank under control of the detector. 21.3.3 Unless otherwise required by the authority having… Continue Reading →

General

Smoke Detection For Fire Alarm Equipment

Posted on June 8, 2018 by Gsurface

  10.15* Protection of Fire Alarm System. In areas that are not continuously occupied, automatic smoke detection shall be provided at the location of each fire alarm control unit(s), notification appliance circuit power extenders, and supervis- ing station transmitting equipment… Continue Reading →

General

Post navigation

Older Articles
Newer Articles
Follow on Instagram
This error message is only visible to WordPress admins

Error: No posts found.

Make sure this account has posts available on instagram.com.

Recent Posts

  • An Introduction to Fire Alarm Systems
  • NICET Fire Alarm Systems Levels 1 & 2 Study Guide
  • 2018 NICET Fire Alarm Systems Level 2 Study Guide
  • 2018 NICET Fire Alarm Systems Level 1 Study Guide
  • NICET Certification Fire Alarm System Pop Quiz Question-Concealed Duct Detector

Recent Comments

    Archives

    • February 2020
    • July 2019
    • June 2019
    • October 2018
    • September 2018
    • July 2018
    • June 2018
    • August 2016
    • March 2016
    • February 2016
    • January 2016
    • December 2015

    Meta

    • Register
    • Log in
    • Entries feed
    • Comments feed
    • WordPress.org

    Categories

    • General
    • News
    • Pop Quiz
    • Videos
    © 2025 Fire Alarms Certified. All rights reserved.
    Hiero by aThemes